The Zedeyes 212  is an economical, industrial-grade electric contact pressure gauge designed for combined pressure monitoring and automatic process switching. Engineered with a durable stainless steel safety case (Version S1 per EN 837) and precision brass movement, it offers a reliable solution for opening or closing electrical circuits based on real-time process pressure levels.

When system pressure reaches or exceeds a pre-configured set-point, the gauge pointer engages the contact arm to either close a circuit (Normally Open / NO) or interrupt a circuit (Normally Closed / NC). This dual-functionality eliminates the need for separate pressure switches and dial gauges, streamlining control panel installation and reducing equipment costs.

Key Features & Benefits

  • Dual Monitoring & Control: Combines local pressure indication with reliable electrical switching in a single instrument.

  • Economical & Durable Design: Features a robust 304 stainless steel case combined with a high-precision brass movement and copper alloy pressure element.

  • Snap-Action Contacts (EC1): Equipped with 70% silver / 30% nickel gold-plated contacts to ensure arc resistance, high conductivity, and long switching service life.

  • Safety Version S1 (EN 837-1): Includes a heavy-duty safety glass window and protective case design engineered according to strict European standard safety guidelines.

  • Versatile Switching Modes: Supports both normally-open (NO) and normally-closed (NC) switching logic to adapt to diversas safety shutdown and system control routines.

  • Flexible Sizing & Pressure Ranges: Available in standard 100 mm and 160 mm nominal dial sizes across extensive measuring spans from 0–1 bar up to 0–600 bar, including compound and vacuum ranges.

Primary Applications

  • Industrial Process Automation: Automatic pump control, motor start/stop triggers, and valve actuation.

  • Alarm & Safety Shutdown Systems: Immediate over-pressure or loss-of-pressure limit switching in utility circuits.

  • Hydraulic & Pneumatic Power Units: Pressure level maintenance and automatic pressure relief control.

  • General Industrial Machinery: Cost-effective pressure monitoring for OEM equipment and factory test benches.

Specification Details
Nominal Sizes 100 and 160 mm
Temperature Ranges −60 to +40, −30 to +50, −20 to +80, 0 to +60, 0 to +100, 0 to +120, 0 to +160, 0 to +200, 0 to +250, 0 to +300, 0 to +400, 0 to +500, 0 to +600 and 0 to +650 °C
Maximum Stem Pressure 20 bar
Temperature Element Gas-actuated Bourdon tube
Storage and Transport Temperature −20 to +60 °C
Permissible Ambient Temperature 0 to +40 °C
Accuracy Class 2 according to EN 13190
Window Instrument glass
Case SS304
Available Capillary Lengths 1, 3, 6 and 10 m
Stem Material SS316
Stem Diameter 10 mm standard; 12 mm optional